System: FIXED LOCAL FIRE FIGHTING SYSTEM {TR-WIND} [550-TRW]
Particulars : Maker : WILHELMSEN SHIPS EQU / Serial No :
Subsystem: Heat Detector [HEAT]
Maker : SALWICO AB
Heat Detector Salwico EV-H/CS 84°C
Function: Heat, thermistor 84°C (also available in 54°C version)
Nominal voltage: 24 VDC
Working voltage: 20-37 VDC
Working current: 0.2 mA
Alarm current: 5 mA
Remote indication: Max 3 mA
Ingress protection: Depends on base
Cable terminals: Depends on base
Temperature range: -25°C to +70°C
Air humidity: 0-95% RH
Material: PC/ABS
Colour: White
Weight (w/o base): ~120 g
Programming tool: Part no. 040300
040005
Subsystem: Manual Call Points [MCP]
maker : SALWICO AB
Manual Call Point IP23 – MCP-A (GB) – With test key
Nominal voltage: 34 VDC
Working voltage: 20-38 VDC
supervising current: 0.2 mA
Alarm current: 2.5 mA
Ingress protection: IP23D
Temperature range: -25?C to +70?C
Ambient humidity: 0 to 95% RH
Material: PC/ABS
Colour: Red, RAL 3001
Weight: ~160 g
Cable dimension: ?6-14 mm
Certified according to: 0470
5200030-01A
03
Manual Call Point IP67 MCP-A WP – With test key
Nominal voltage: 34 VDC
Working voltage: 20-38 VDC
Supervising current: 0.2 mA
Alarm current: 2.5 mA
Ingress protection: IP67
Temperature range: -25?C to +70?C
Ambient humidity: 0 to 95% RH
Material: PC/ABS
Colour: Red, RAL 3001
Weight: ~240 g
Cable dimension: ?6-14 mm
Certified according to: 0470
5200031-01A
Subsystem: SMOKE DETECTORS [smoke]
Maker : WILHELMSEN SHIPS EQU
04
Optical Smoke Detector – Salwico EV-P
Function: Analogue, addressable, scattering light
Nominal voltage: 24 VDC
Working voltage: 20-37 VDC
Working current: 0.2 mA
Alarm current: 5 mA
Remote indication: Max 3 mA
Ingress protection: Depends on base
Cable terminals: Depends on base
Temperature range: -25°C to +70°C
Air humidity: 0-95% RH
Material: PC/ABS
Colour: White
Weight (w/o base): ~120 g
Programming tool: Part no. 040300